ClearShield’s fire attenuation screens have been designed for applications to satisfy the requirements of AS1530.4-2014. ClearShield’s Fire Attenuation Screens are an economical alternative to conventional drenching (sprinkler) systems, and they also offer a high level of security.
ClearShield Australia contracted the services of Warrington Fire Research Australia to test the ClearShield’s Fire Attenuation Screen and when tested, achieved a reduction of radiant heat of 52.3kW/m2 when exposed to Boundary* conditions (80kW/m2). That’s a massive 65% Attenuation of heat in the worst possible conditions (as indicated in the NCC)
ClearShield also offer a range of bushfire screens and bushfire shutters.
Aluminium Framing | |
---|---|
Grade: | 6063 – T6 |
Coating: | Anodised – min 15um to AS1213- |
Powdercoating – Chromate Pre-treatment and powdercoated to AS3715-2002 | |
Warranty: | As per Coating Selection |
Stainless Steel Sheet | |
---|---|
Grade: | T304-2b |
Finish: | Satin Black Powder Coated |
Warranty: | 15 Years, subject to adhering to the recommended cleaning schedule |
Coating: | Powdercoating – Oxsilane Chrome Free Pre-treatment and powdercoated to AS3715-2002 |
Open Area: | 39%-41% |
Dimensions: | Domestic Grade Ø 2mm Round Holes, 60° Staggered Pitch, 3mm Spacings, 1.0mm Thick |
Standard | Date of test | Test No. | Details | Result |
---|---|---|---|---|
AS1530.2014 | 44497 | FRT210115 | Test of CS Screen over 130mins exposed to 80kW/m² | AVG Transmitted Radiation 27kW/m^{2}, AVG Blocked Irradiance 65% |